AFR / AFR-M
Beton dolgulu panellerle kullanılmak üzere tasarlanmış AFR ve AFR-M taşıyıcı ayak grubu.
KAYNAK: AUCO 2026 KATALOĞU · SAYFA 18, 19, 20
Ürün hakkında teklif alın
Katalog açıklamaları
PDF metni orijinal İngilizce dilinde aktarılmıştır; çok sütunlu sayfalarda okuma sırası değişebilir. Teknik kararlar için aşağıdaki orijinal sayfayı esas alın.
Katalog sayfa 18 — açıklama ve teknik bilgiler
The AFR Footing Group is a special raised floor footing designed exclusively for use with concrete infill panels. Featuring an imported (Chinese-made) substructure, the product offers flexibility to projects with three different usage alternatives: AFR AFR-M In AFR models without plastic, the use of bracing is mandatory. Bracing is mounted to the feet to form a frame; concrete infill panels are placed within this frame and secured to the foot by screwing. In the version without bracing, the panels are securely mounted by screwing them to the foot at all four corners after being placed on the foot. Offering a long-lasting, robust, and functional substructure in concrete infill floor applications, the AFR Footing is a special solution for raised floor systems. AFR
Katalog sayfa 19 — açıklama ve teknik bilgiler
AFR / TECHNICAL Technical Data: Element class according to DIN EN 12825: 6 Single Load: M14, ≥ 3 kN M16, ≥ 4 kN M18, ≥ 5 kN Distributed Load: M14, ≥ 7 kN M16, ≥ 9 kN M18, ≥ 12 kN Breaking Load: M14, ≥ 8 kN M16, ≥ 11 kN M18, ≥ 14 kN Head: Head plate dimensions: 80 × 80 × 2.5 mm The head is made of Ø21 × 1.5 mm steel pipe. The AFR head can be used with or without bracing on encapsulated panels, PVC panels and wooden panels. Base and Rod: Base plate dimensions: 90 × 90 × 2 mm Steel Adjustment Rod: M14×1.25 thread, 117 mm rod length (M14, M16, M18) The rod is mounted to the base plate using a rolling (tight fit) method. Precise height adjustment can be made thanks to the (M14, M16, M18) nut. Load Capacity (System): Single load capacity: M14 ≥ 3 kN (~300 kg) M16 ≥ 4 kN (≈ 400 kg) M18 ≥ 5 kN (≈ 500 kg) Distributed load capacity: M14 ≥ 7 kN (~700 kg) M16 ≥ 9 kN (≈ 900 kg) M18 ≥ 12 kN (≈ 1200 kg) Breaking load: M14 ≥ 8 kN (~800 kg) M16 ≥ 11 kN (≈ 1100 kg) M18 ≥ 14 kN (≈ 1400 kg)
Katalog sayfa 20 — açıklama ve teknik bilgiler
AFR - M / TECHNICAL Technical Data: Element class according to DIN EN 12825: 6 Single Load: ≥ 4 kN (~400 kg) Distributed Load: ≥ 9 kN (~900 kg) Breaking Load: ≥ 11 kN (~1100 kg) Head: Head plate dimensions: 80 × 80 × 2.5 mm AFR head is mounted by rolling with M18 or M20 × 130 mm rod, height adjustment can be made with M18 or M20 nut. Base and Rod: Base plate dimensions: 90 × 90 × 2 mm Steel Adjustment Rod: M14×1.25 thread, 117 mm rod length (M14, M16, M18, M20) The rod is mounted to the base plate using a roll-fit (tight fit) method. Pipe Diameter Dimensions: Ø25 x 2 mm Adjustment and Fixing: After making the appropriate height adjustment, the adjustment nut at the connection point between the head and the foot is fixed with Loctite 243 or equivalent adhesive.